7-1/2 Ton 208/230 Volt 3-Phase Hermetic Commercial Compressor.(Copeland) (ROTOLOCK Fittings)

Suitable for air conditioning, R22 applications charged with mineral oil.

• RL (R suffix) connection requires valves or adapters, not provided
• Mount: 8.7" x 8.7"
• Capacity rated: 45°F evaporator; 130°F condensing

Horsepower: 7 1/2
Voltage: 208-230/3/60
Rated Load Amps: 30.1
Oil: Mineral
Mount (In.): 8.7 x 8.7
Height (In.): 18.4
Shipping Weight (Lbs.): 169
Connection Suction (In.): 1 3/4 RL
Connection Discharge (In.): 1 1/4 RL
Connection Type: Rotolock
Refrigerant: R22
Capacity (BTUH): 97,000
Engineered Items: Yes
LTL Only: Yes
Oil_short: MIN
Sort: 1
Specials: No
Vendor: Copeland Corporation

Replaces Compressor Part Numbers:

BRE20750TFCR BRE-207502-TFC BRE2-07502-TFCR CARBRE207502TFC CARBRD20750TFC902R.

* IMPORTANT!!! - PLEASE NOTE: IDENTIFYING COMPRESSOR FAILURES

Most compressors fail due to system malfunctions, which must be corrected to prevent repeat failures. After a compressor fails, field examination of the failed compressor often will reveal symptoms of system problems. Proper corrections will help eliminate future failures.

* SINGLE PHASE BURN

Two phases of a three-phase motor overheated or burned as a result of the contactor opening only one of its contacts.

Correction:

(1) Replace contactors with properly sized contactors.
(2) Check for proper motor protection.

* HALF WINDING SINGLE PHASE BURN

In a two contactor application, two phases of one half of a three phase motor overheated or burned as a result of one contactor opening only one contact.

Correction:

(1) Replace contactors with properly sized contactors.

* HALF WINDING BURN

Half of all phases on a two contactor three phase motor are overheated or burned due to only one contactor opening.

Correction:

(1) Replace contactors with properly sized contactors.
(2) Check for feed back circuit holding one contactor closed.

* PRIMARY SINGLE PHASE BURN

Only one phase of a three phase motor is overheated or burned as the result of opening one phase on the primary side a delta to wye transformer.

Correction:

(1) Check primary side of a delta to wye main power transformer.

* START WINDING BURN

The start winding only of a single-phase motor is uniformly overheated or burned.

Correction:

(1) Check for proper wiring of compressor.
(2) Check starting capacitor and/or starting relay.
(3) Correct compressor overloading.

* SPOT BURN

A localized burn within a winding, between windings, or from windings to ground. If not the result of mechanical problems, check for spikes or surges of high current flow.

* SHORTED TERMINALS

A break down of the insulation between terminals and compressor body generally the result of over torque terminals.

OPTIONAL PARTS LISTED BELOW: