3 Ton 34,000 Btuh 208/230 Volt 1-Phase Compressor R-22 Refrigerant (Copeland)

3 Ton 34,000 Btuh 208/230 Volt 1-Phase Compressor R-22 Refrigerant (Copeland)
Code: COMP34KQPVF
Price: $886.00
Quantity in Basket: None
Quantity:
* Copland Hermetic Compressor

* Installation

When installing your new compressor, you may need additional copper fittings and tubing in some older model compressors when retro-fitting to new upgraded compressor models.

* Compressor Performance:

Voltage: 208/230
Phase: 1
Tons: 3
Capacity (Btu/hr): 34,000
Refrigerant: 22
Compressor Foot Mounting: 7-1/2" x 7-1/2”
Suction Size (in): 3/4"
Discharge size (in): 3/8"

BtuH Ratings are based 0n 45 F evaporating temperature 130 F, condensing temperature, 65 F return gas temperature and 95 F, liquid temperature.

Replaces Compressor Part Numbers:

1050814, COMP34KSPVF230, CRH30275-PFV-270, CRH30275PFV270, CR34KQPFV980WB, CR34KF-PFV, CR34KF-PFV-130, CR34K3-PFV-230, 2R34K3-PFV-230, CR34KQ-PFV-980WB, CR34KQ980-W, CR34KQ-PFV, CARB93389, CAR4D664, CARCR34KQ980W.

* IMPORTANT!!! - PLEASE NOTE: IDENTIFYING COMPRESSOR FAILURES

Most compressors fail due to system malfunctions, which must be corrected to prevent repeat failures. After a compressor fails, field examination of the failed compressor often will reveal symptoms of system problems. Proper corrections will help eliminate future failures.

* SINGLE PHASE BURN

Two phases of a three-phase motor overheated or burned as a result of the contactor opening only one of its contacts.

Correction:

(1) Replace contactors with properly sized contactors.
(2) Check for proper motor protection.

* HALF WINDING SINGLE PHASE BURN

In a two contactor application, two phases of one half of a three phase motor overheated or burned as a result of one contactor opening only one contact.

Correction:

(1) Replace contactors with properly sized contactors.

* HALF WINDING BURN

Half of all phases on a two contactor three phase motor are overheated or burned due to only one contactor opening.

Correction:

(1) Replace contactors with properly sized contactors.
(2) Check for feed back circuit holding one contactor closed.

* PRIMARY SINGLE PHASE BURN

Only one phase of a three phase motor is overheated or burned as the result of opening one phase on the primary side a delta to wye transformer.

Correction:

(1) Check primary side of a delta to wye main power transformer.

* START WINDING BURN

The start winding only of a single-phase motor is uniformly overheated or burned.

Correction:

(1) Check for proper wiring of compressor.
(2) Check starting capacitor and/or starting relay.
(3) Correct compressor overloading.

* SPOT BURN

A localized burn within a winding, between windings, or from windings to ground. If not the result of mechanical problems, check for spikes or surges of high current flow.

* SHORTED TERMINALS

A break down of the insulation between terminals and compressor body generally the result of over torque terminals.