Two Rod Direct Spark Ignition Control with 4 second trial time and 4 second lock out timing

Two Rod Direct Spark Ignition Control with 4 second trial time and 4 second lock out timing
Code: IGM89F1098
Price: $226.74
Quantity in Basket: None
Quantity:
Two Rod Direct Spark Ignition Control with 4 second trial time and 4 second lock out timing.

Product Specifications:

Ignition System Type: Direct Spark Ignition.
Ignition Sequence: Single trial for main burner ignition [then shut down and lockout].
Typical Gas Control: VR8205, VR8305.
Type of Gas Natural or LP.
Flame Sense Two Rods.
Ignition Source External (120 VAC powered) High Voltage Spark Generator.
PrePurge 30 sec. minimum.
Ignition Trials To Lockout 1.
Lockout Timing 4 sec..
Ignition Trial Time (sec) 4 sec..
Maximum Valve Load @ 24 Vac (Amps) 2A.
Typical Ignition Hardware Q652, Q345 Dimensions (in.) 5 1/4 in. high x 4 1/16 in. wide x 1 15/16 in. long.
Dimensions (mm) 133 mm high x 103 mm wide x 49 mm deep.
Electrical Ratings 24 Vac.
Frequency 60 Hz.
Maximum Ambient Temperature (F) -40 F to +175 F.
Maximum Ambient Temperature (C) -40 C to +79 C.
Approvals, Canadian Standards Association Design Certified.
Flame Failure Response Time (sec) 2.0 sec. @ 2.5 microamp.
Flame Failure Re-ignition Time (sec) 0.8 sec. maximum.
Replaces Part Numbers: S89F1098, CARS89F1098