4 Ton Air Conditioning Compressor 200/240 Volts 3-Phase.(Copeland)

4 Ton Air Conditioning Compressor 200/240 Volts 3-Phase.(Copeland)
Code: COMP47KQTF5
Price: $956.00
Quantity in Basket: None
Quantity:
* Copland Commercial Compressor



WHEN PLACING YOUR PARTS ORDER, YOU CAN ORDER ONLINE 24 HOURS A DAY OR BY CALLING OUR SALES CENTER MONDAY THROUGH FRIDAY 7AM TO 5PM PACIFIC TIME. WE WILL SHIP YOUR PART FROM THE CLOSEST WAREHOUSE PER YOUR ZIP CODE. WE CAN SHIP YOUR PARTS TO YOU NEXT DAY AIR, SECOND DAY AIR OR 3 DAY SELECT OR U.S. POST OFFICE, AND WHEN PLACING YOUR ORDER ONLINE SHIPPING ESTIMATES WILL BE PROVIDED TO YOU FOR EACH SHIPPING CLASS.


* Compressor Performance:

Evap (F)/Cond (F):45/130
RG (F) Liq (F): 65/115
Capacity (Btu/hr): 40500
Power (Watts): 4030
Current Amps: 15.2
EER (Btu/Wh): 10.0
Mass Flow (Lbs/hr): 595
Sound Power (Dba):74.0
Vibration (mils (peak-peak): 2.5 AVE

* Compressor Mechanical:

Number of Cylinders:2
Bore Size (in): 1.96
Stroke (in): 0,821
Overall Length:10.375"
Overall Width: 9.094
Overall Height:14.812
Suction Size (in): 7/8"
Discharge size (in): 1/2"
Initial Oil Charge (oz): 45
Oil Recharge (oz): 43
CIR (in 3/Rev): 4.954
CFH (ft 3/hr):498.8482.

* Compressor Electrical Data:

Voltage: 200/240
Phase: 3
RLA: 16.0
LRA: 97.0
MCC Amps:
RPM:
Max Operating Current:
UL File No:
Replaces Part Numbers:
CR47KQTF5980WB 015-03464-005 01503464005 04DG1124B S51417 P128833 PCR47KQ-TF5 PCR47KQTF5 1059518 P021-4751 P0214751 CRL3-0350-TF5 CRL0350TF5 A093 CRL0-0350-TF5-523 CRLO-0350-TF5-523 CRLO-0350-TF5 CRL0-0350-TF5 CR47KQ-TF5-980WB CR47KQ-TF5 H23A423DBLA B9266-204A CARB9266204A CARB93395 CARCR47KQTF5B92

Used in Goodman, Janitrol Air Conditioning Models: CK49-3, CPKE48-3, CPLE048-3, PCK048-3, PHK048-3, PGB048100-3, PGB048150-3.

* IMPORTANT!!! - PLEASE NOTE: IDENTIFYING COMPRESSOR FAILURES

Most compressors fail due to system malfunctions, which must be corrected to prevent repeat failures. After a compressor fails, field examination of the failed compressor often will reveal symptoms of system problems. Proper corrections will help eliminate future failures.

* SINGLE PHASE BURN

Two phases of a three-phase motor overheated or burned as a result of the contactor opening only one of its contacts.

Correction:

(1) Replace contactors with properly sized contactors.
(2) Check for proper motor protection.

* HALF WINDING SINGLE PHASE BURN

In a two contactor application, two phases of one half of a three phase motor overheated or burned as a result of one contactor opening only one contact.

Correction:

(1) Replace contactors with properly sized contactors.

* HALF WINDING BURN

Half of all phases on a two contactor three phase motor are overheated or burned due to only one contactor opening.

Correction:

(1) Replace contactors with properly sized contactors.
(2) Check for feed back circuit holding one contactor closed.

* PRIMARY SINGLE PHASE BURN

Only one phase of a three phase motor is overheated or burned as the result of opening one phase on the primary side a delta to wye transformer.

Correction:

(1) Check primary side of a delta to wye main power transformer.

* START WINDING BURN

The start winding only of a single-phase motor is uniformly overheated or burned.

Correction:

(1) Check for proper wiring of compressor.
(2) Check starting capacitor and/or starting relay.
(3) Correct compressor overloading.

* SPOT BURN

A localized burn within a winding, between windings, or from windings to ground. If not the result of mechanical problems, check for spikes or surges of high current flow.

* SHORTED TERMINALS

A break down of the insulation between terminals and compressor body generally the result of over torquing terminals.