Commercial 5.0 Ton Air Conditioning and Heat Pump Compressor.(460 Volt 3-Phase)

Commercial 5.0 Ton Air Conditioning and Heat Pump Compressor.(460 Volt 3-Phase)
Code: COMP23A623DBEA
Price: $998.00
Quantity in Basket: None
Quantity:
* Bristol Commercial Compressor *

* Compressor Mechanical Performance:

Capacity (Btu/hr):60800
Current Amps:
Overall Length:"
Overall Width: “
Overall Height: 16-1/8“
Suction Size (in): 7/8"
Discharge size (in): 1/2"
Refrigerant: R-22
* Compressor Electrical Data:

Voltage:460
Phase:3
RLA:
LRA:

Replaces Older Compressor Part Numbers:

B9266657, P032-5781, H25A65QDBEA, 703020-3000-00; GB20KL001, H2DA563DBEA, H245A83DBEA, H73A463DBEA, CARB81254, H23A623DBEA CARB9266657.

Used in Air Conditioning Models:

PGB060150-4, 48TMF006100 0043 580FTV060150AB 0043 48TJF006110 0037 48TFF006110 0043 48TJF012120 0038 580FTV060115AB 0043 48TME006100 0043 558FTX060000AA 0043 48TJE012120 0038 48TFE006110 0043 48TJE006110 0037 48TFF006100 0043 50TM006100 0043 580FTV060115AA 0043 580FTV060150AA 0043 48TFE006100 0043 580DTV060150ABAA 0037 580DTV060115ABAA 0037 50TFF006110 0043 558DTX060000AB 0037 50TJ006110 0037 580DTV120250AC 0038 50TFF006100 0043 580DTV120180AC

* IMPORTANT!!! - PLEASE NOTE: IDENTIFYING COMPRESSOR FAILURES

Most compressors fail due to system malfunctions, which must be corrected to prevent repeat failures. After a compressor fails, field examination of the failed compressor often will reveal symptoms of system problems. Proper corrections will help eliminate future failures.

* SINGLE PHASE BURN

Two phases of a three-phase motor overheated or burned as a result of the contactor opening only one of its contacts.

Correction:

(1) Replace contactors with properly sized contactors.
(2) Check for proper motor protection.

* HALF WINDING SINGLE PHASE BURN

In a two contactor application, two phases of one half of a three phase motor overheated or burned as a result of one contactor opening only one contact.

Correction:

(1) Replace contactors with properly sized contactors.

* HALF WINDING BURN

Half of all phases on a two contactor three phase motor are overheated or burned due to only one contactor opening.

Correction:

(1) Replace contactors with properly sized contactors.
(2) Check for feed back circuit holding one contactor closed.

* PRIMARY SINGLE PHASE BURN

Only one phase of a three phase motor is overheated or burned as the result of opening one phase on the primary side a delta to wye transformer.

Correction:

(1) Check primary side of a delta to wye main power transformer.

* START WINDING BURN

The start winding only of a single-phase motor is uniformly overheated or burned.

Correction:

(1) Check for proper wiring of compressor.
(2) Check starting capacitor and/or starting relay.
(3) Correct compressor overloading.

* SPOT BURN

A localized burn within a winding, between windings, or from windings to ground. If not the result of mechanical problems, check for spikes or surges of high current flow.

* SHORTED TERMINALS

A break down of the insulation between terminals and compressor body generally the result of over torquing terminals.