Copeland Replacement Compressor 200/230 Volts 1-Phase

Copeland Replacement Compressor 200/230 Volts 1-Phase
Code: COMP12K6EPFV
Price: $898.00
Quantity in Basket: None
Quantity:
* Copland Commercial Compressor

* Compressor Performance:

Evap (F)/Cond (F):
RG (F) Liq (F)
Capacity (Btu/hr):
Power (Watts):
Current Amps:
EER (Btu/Wh):
Mass Flow (Lbs/hr):
Sound Power (Dba):70 AVE
Vibration (mils (peak-peak):1.8

* Compressor Mechanical:

Number of Cylinders: 2
Bore Size (in):1.516
Stroke (in): 0.703
Overall Length:10.28"
Overall Width:9.09
Overall Height: 13.31
Suction Size (in): 3/4
Discharge size (in):3/8
Initial Oil Charge (oz): 45
Oil Recharge (oz): 43
CIR (in 3/Rev):
CFH (ft 3/hr):

* Compressor Electrical Data:

Voltage: 200
Phase: 1
RLA: 10.9
LRA: 56.0
MCC Amps: 15.3
RPM:
Max Operating Current:
UL File No:
Replaces Bristol Refrigeration Compressor.
Replaces Part Numbers:CS12K6EPFV970 CS12K6E-PFV, L51B452BBCB, CARCS12K6EPFV.

* IMPORTANT!!! - PLEASE NOTE: IDENTIFYING COMPRESSOR FAILURES

Most compressors fail due to system malfunctions, which must be corrected to prevent repeat failures. After a compressor fails, field examination of the failed compressor often will reveal symptoms of system problems. Proper corrections will help eliminate future failures.

* SINGLE PHASE BURN

Two phases of a three-phase motor overheated or burned as a result of the contactor opening only one of its contacts.

Correction:

(1) Replace contactors with properly sized contactors.
(2) Check for proper motor protection.

* HALF WINDING SINGLE PHASE BURN

In a two contactor application, two phases of one half of a three phase motor overheated or burned as a result of one contactor opening only one contact.

Correction:

(1) Replace contactors with properly sized contactors.

* HALF WINDING BURN

Half of all phases on a two contactor three phase motor are overheated or burned due to only one contactor opening.

Correction:

(1) Replace contactors with properly sized contactors.
(2) Check for feed back circuit holding one contactor closed.

* PRIMARY SINGLE PHASE BURN

Only one phase of a three phase motor is overheated or burned as the result of opening one phase on the primary side a delta to wye transformer.

Correction:

(1) Check primary side of a delta to wye main power transformer.

* START WINDING BURN

The start winding only of a single-phase motor is uniformly overheated or burned.

Correction:

(1) Check for proper wiring of compressor.
(2) Check starting capacitor and/or starting relay.
(3) Correct compressor overloading.

* SPOT BURN

A localized burn within a winding, between windings, or from windings to ground. If not the result of mechanical problems, check for spikes or surges of high current flow.

* SHORTED TERMINALS

A break down of the insulation between terminals and compressor body generally the result of over torquing terminals.